Siemens SIMODRIVE 611 universal Function Manual page 796

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

A Lists
A.1
Parameter list
1001
Speed controller cycle
Min
Standard
2
4
Speed controller cycle = P1001 x 31.25 microseconds
Note:
Current controller clock cycle <= speed controller clock cycle
refer to the index entry "Clock cycles"
1004
Structure configuration
Min
Standard
0
100
... allows the closed-loop control structure to be configured.
Bit 4
Integrator control
Bit 4 = 1
Integrator control in the speed controller inactive
The integrator is not held, but its absolute value is limited to twice the torque limit.
Bit 4 = 0
Integrator control in the speed controller active
The integrator is held, if the speed controller, current controller or the voltage has
reached its limit.
Bit 8
Fine interpolation in positioning mode (P0700 = 3) (from SW 3.1)
Bit 8 = 1
The fine interpolation type II is active (standard from SW 3.1)
Bit 8 = 0
Fine interpolation, type I is active (standard before SW 3.1)
Bit 9
Deadtime adjustment position ref. value coupling via PROFIBUS-DP
(from SW 4.1)
Bit 9 = 1
Same deadtime behavior as the slave drive (standard from SW 4.1)
Prerequisite: Drive is not a slave drive (P891 = –1)
Output of position reference value XsollP (50208).
Bit 9 = 0
Minimum deadtime behavior (standard before SW 4.1)
1005
IM encoder pulse number (SRM ARM)
Min
Standard
0
2048
Note:
IM ––> Indirect measuring system (motor encoder)
If the encoder pulse number cannot be divided by 10 or 16 without a remainder, the zero mark
monitoring is internally disabled.
1006
IM encoder code number
Min
Standard
0
0
The encoder number defines the connected measuring system.
Note:
IM ––> Indirect measuring system (motor encoder)
refer to the index entry "Encoder code"
1007
DM encoder pulse number (SRM ARM)
Min
Standard
0
0
Note:
DM ––> Direct measuring system
Encoder pulses for indirect measuring system (IM, motor encoder) ––> refer to P1005
If the encoder pulse number cannot be divided by 10 or 16 without a remainder, the zero mark
monitoring is internally disabled.
A-796
Max
Unit
16
31.25µs
Max
Unit
315
Hex
Max
Unit
65535
Max
Unit
65535
Max
Unit
8388607
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
! 611ue diff !
Data type
Effective
Unsigned16
PO
Data type
Effective
Unsigned16
PO
Data type
Effective
Unsigned16
PO
Data type
Effective
Unsigned16
PO
Data type
Effective
Unsigned32
PO
E Siemens AG 2005 All Rights Reserved
04.05
01.99
(SRM ARM)
(–> 3.3)
(SRM ARM)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents