6.11.4

Changeover, max. 2 motors each with 2 data sets (P1013 = 3)

Description
For this changeover version (P1013 = 3) a maximum of 2 motors each
with 2 associated motor data sets can be changed over.
The changeover is realized using the input terminal with function num-
ber 6 and using the appropriately selected speed thresholds in P1247
or P1248. At changeover, the absolute speed value is considered.
Changeover is also possible during operation. When changing over be-
tween star and delta operation, it is possible to additionally select be-
tween eight drive parameter sets [0...7].
Input/output
The following input/output signals are used for this changeover version:
signals
Table 6-64
1) If the input terminal is used to change over the motor, then the pulses are
2) The input terminal with function number 5 is inactive for this changeover
3) The pulses are not canceled if changeover is realized using speed
4) Output terminals with function numbers 12 and 14 are not energized.
Note
Output terminals 11 and 13 are not energized, if P1249 = 1.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
6.11 Motor changeover for induction motors (from SW 2.4)
Input/output terminal signals
Input terminal
Speed
with
threshold
function No.
1)
2)
6
5
n < P1247
0
0
n > P1247
n < P1248
1
1
n > P1248
canceled at the changeover.
version.
thresholds.
6 Description of the Functions
Effective
Output terminal
3)
motor data
set
function No.
4)
14
13
P1xxx
0
P2xxx
0
P3xxx
0
P4xxx
0
with
4)
12
11
0
0
1
0
0
1
1
0
0
1
0
0
6-589