Permanent–magnet synchronous motor with field–weakening (PE spindle)
3. Set PE specific parameters and activate the PE spindle (only for
Note
This completes the basic commissioning.
The motor can be operated with these settings.
After this first commissioning, for reasons of accuracy, the rotor
position identification run must be executed with zero mark and the
angular commutation offset determined.
Reader's note
Additional commissioning instructions/information regarding motor
optimization are provided in the following.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
unlisted motors)
– Enter or change the following parameters via the expert list.
P No.
Name
1136
Motor short–circuit current
1142
Speed at the start of field weaken-
ing
1015
Activate PE–MSD
– Execute the "calculate controller data" function
After this, the controller data is pre–assigned, PE–specific.
– Save the parameters in the FEPROM
– Carry–out a POWER–ON RESET
4 Commissioning
Value
Units
A(rms)
RPM
1: Activated
0: De–acti-
vated
4-157