Online Operation: Simocom U Via Profibus-Dp (From Sw 3.1) - Siemens SIMODRIVE 611 universal Function Manual

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

01.99
06.04
3.3
Parameterizing using the parameterizing and start–up tool SimoCom U
3.3.4
Online operation: SimoCom U via PROFIBUS–DP (from SW 3.1)
Description
The "SimoCom U" parameterizing and start–up tool can communicate
with the drives via the serial interfaces and also via the PROFIBUS–DP
fieldbus.
The following online modes are possible:
S
S
If the subsequently listed prerequisites are fulfilled, then online oper-
ation can be established between SimoCom U, and all of the drives
connected to the bus ("DP slaves 611U").
Settings for
For SimoCom U, communications via PROFIBUS–DP can be set as
SimoCom U
follows:
S
S
Then, online operation can be established directly to the drive via the
fieldbus using the "Search for online drives" function.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Online operation via the CP 5511/CP 5611/CP 5613 directly with the
fieldbus
PC/PG <––> CP 5511 / CP 5611 / CP 5613 <––> PROFIBUS <––>
drives
Online operation via the MPI interface of SIMATIC S7
PC/PG <––> MPI <––> PROFIBUS <––> drives
Options – Settings – Communications ––> "Interface" dialog"
For "For "Go online" connect via" set the following:
––>
"PROFIBUS" and
––>
"Direct connection"
––> if the coupling is directly with the field bus
or
––>
"MPI –> PROFIBUS Routing"
––> if the coupling is via the MPI interface
or
––>
"Communication via OPC server" (from SW 6.1)
––> if the coupling is via OPC server