Advertisement

4 Commissioning
4.5
Function–initiating and diagnostic parameters
Table 4-2
Function–initiating parameters, continued
No.
1084
Start motor data optimization (ARM)
... starts the "motor data optimization" function, which is set in P1083.
0
Inactive or exited fault–free
1
Start motor data optimization
Note:
At the end, 0 or a fault code is automatically written into the parameter.
Fault code:
–2
–3
–4
–5
–6
–7
–8
–9
–11
–12
–13
–14
–15
–16
Diagnostic
parameters
Table 4-3
Diagnostic parameters
No.
0599
Active motor data set (from SW 2.4)
... indicates whether the motor changeover has been enabled, or which motor data set is active.
0
Motor changeover inhibited (P1013 = 0)
1
Motor data set 1 (P1xxx) active
2
Motor data set 2 (P2xxx) active
3
Motor data set 3 (P3xxx) active
4
Motor data set 4 (P4xxx) active
Note:
Motor changeover is described in Chapter 6.11.
4-134
Parameters
Name
A pulse frequency (P1100) of 4 kHz or 8 kHz is required
Controller/pulse enable missing
Speed setpoint <> 0
Motor is presently being changed–over
Error when determining the leakage inductance (result) < 0)
V/f mode is active
The incorrect motor was selected because of the motor changeover
Parameterized maximum speed is too low for the measurement
Changeover speed, open–loop/closed–loop control is too high (P1466)
Speed range too low (P1466 or P1160 too high)
Ramp–function generator enable missing
Open–loop torque controlled mode is selected
Motor data optimization for the listed motor not permissible (from SW 3.3)
Excessively high current results in limiting by the i2t power module model
Diagnostic parameters are display parameters, i.e. they can only be
read.
The following parameters are used for diagnostics:
Parameters
Name
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Min.
Standard
0
0
1
Min.
Standard
E Siemens AG 2005 All Rights Reserved
01.99
04.99
Max.
Units
Effective
Immedi-
ately
Max.
Units
Effective
hex
RO

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents