Siemens SIMODRIVE 611 universal Function Manual page 176

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

4 Commissioning
4.10 Linear motors (1FN1, 1FN3 motors)
1FN1 linear motor
If the EnDat serial number
read from the measuring system
is not equal to P1025, then P1017
is automatically set to 1
When the enable signals are present, a rotor position
identification routine is immediately carried-out. If the
rotor position identification was not successful,
the appropriate fault message is output. If the
causes of the fault are removed and the
fault message acknowledged, a new
identification attempt is made.
The angular commutation offset
Fig. 4-13 Absolute measuring system
4-176
For an absolute measuring system:
START
Motor type?
Yes, limitations fulfilled
(P1075 must be set to 3!)
Set P1017 to 1
acknowledge alarm 604
is automatically entered
into P1016
END
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
1FN3 linear motor
If the EnDat serial number read from
the measuring system is not equal to
P1025, then P1017 is not set and
Alarm 604 is displayed
("motor encoder is not adjusted")
Limitations for
motion–based rotor
position identification fulfilled?
No, limitations
not fulfilled
The angular commutation offset must be
determined by making the appropriate measurem.
(refer to Chapter 4.10.8) and manually
entered into P1016
Set P1017 to –1
The EnDat serial number is
read–out of the measuring system and
automatically entered into P1025
Alarm 799 is displayed
Save parameters and
carry–out a POWER–ON RESET
E Siemens AG 2005 All Rights Reserved