Siemens SIMODRIVE 611 universal Function Manual page 308

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

5 Communications via PROFIBUS DP
5.9
Parameter overview of PROFIBUS–DP
Table 5-38
Parameters for PROFIBUS–DP, continued
No.
0918
PROFIBUS node address
... specifies the address of the drives as DP slave on PROFIBUS.
Note:
S
There is one node address for the control board, although it is designed for two drives.
When changing the parameter in one drive, the parameter in the other drive is automati-
cally adapted.
S
Every node connected to PROFIBUS must have a unique address.
0922
Telegram selection PROFIBUS
(from SW 3.1)
... is used to set the free configurability or to select a standard telegram.
––> Refer to Chapter 5.6.5
0945:65
Fault code
... the fault code, i.e. the number of the fault which occurred, is entered.
The faults which occurred, are entered as follows into the fault buffer:
– first fault which occurred ––> parameter with index 1
to
– Eight faults which occurred
Note:
S
The following belongs to a fault:
Fault code (P0945:65), fault number (P0947:65), fault time (P0948:65) and fault value
(P0949:65)
S
A description of the faults, the way in which they can be acknowledged as well as a list of
all the faults, is provided in Chapter 7.
S
This parameter is reset at POWER ON.
0947:65
Fault number
Note:
This parameter is of no significance.
0948:65
Fault time
This parameter specifies at which relative system time, the fault occurred.
Note:
This parameter is set to zero at POWER ON, and the time is then started.
0949:65
Fault value
The supplementary information associated with a fault which occurred, is entered in this pa-
rameter.
Note:
S
A description of the faults, the way in which they can be acknowledged as well as a list of
all the faults, is provided in Chapter 7.
S
This parameter is reset at POWER ON.
5-308
Parameters
Description
––> parameter with index 8
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Min.
Stan-
Max.
dard
0
0
126
0
101
104
E Siemens AG 2005 All Rights Reserved
04.99
04.99
04.99
04.99
08.99
Units
Effec-
tive
PO
PO
RO
RO
ms
RO
RO

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simodrive 611 universal e

Table of Contents