7 Fault Handling/Diagnostics
7.3
List of faults and warnings
035
Cause
Remedy
Acknowledgement
Stop response
036
Cause
Remedy
Acknowledgement
Stop response
037
Cause
Remedy
Acknowledgement
Stop response
7-634
Error when saving the user data. Supplementary info:
\%X
An error occurred when saving the user data in the FEPROM on the
memory module.
Cause: Data transfer error, FEPROM memory cell defective
Note: The user data which was last saved, is still available as long as a
new data backup was unsuccessful.
Supplementary information: only for siemens-internal error diagnostics
Initiate another data backup.
If data backup is still unsuccessful after several attempts, then the
memory module must be replaced. If the user data, valid up to the er-
ror, is to be used in the new memory module, then it must be read out
via SimoCom U before the memory module is replaced, and loaded
again after it has been replaced.
POWER ON
STOP II (SRM, SLM) STOP I (ARM)
Error when downloading the firmware. Suppl. info: \%X
An error occurred when loading a new firmware release.
Cause: Data transfer error, FEPROM memory cell defective
Note: As the previously used firmware was erased when downloading,
the drive expects a new firmware download after RESET or POWER
ON.
Supplementary information: only for siemens-internal error diagnostics
Execute RESET or POWER ON.
If a download is still unsuccessful after several attempts, the memory
module must be replaced. If this is unsuccessful the control module is
defective and must be replaced.
POWER ON
STOP II (SRM, SLM) STOP I (ARM)
Error when initializing the user data. Supplementary
info: \%X
An error occurred when loading the user data from the memory module.
Cause: Data transfer error, FEPROM memory cell defective
Supplementary information: only for siemens-internal error diagnostics
Execute POWER ON.
If a download is still unsuccessful after several attempts, the memory
module must be replaced. If this is unsuccessful the control module is
defective and must be replaced.
POWER ON
STOP II (SRM, SLM) STOP I (ARM)
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
E Siemens AG 2005 All Rights Reserved
04.05
01.99