Siemens SIMODRIVE 611 universal Function Manual page 132

Control components for closed-loop speed control and positioning
Table of Contents

Advertisement

4 Commissioning
4.5
Function–initiating and diagnostic parameters
Table 4-2
Function–initiating parameters, continued
No.
0659
Boot
... it is possible to toggle between the boot and standard state.
0
Establish the boot state
Sequence:
Remove write protection (P0651 = 4), establish the boot state (P0659 = 0), write into
the FEPROM (P0652 = 1), hardware POWER–ON RESET
Only the following parameters can be selected and changed in the boot state (first
commissioning):
– P1106 (power module code number), if it was not automatically identified
– P1102 (motor code number)
– P1006 (IM encoder code number)
– P0700 (operating mode)
– P0918 (PROFIBUS node address)
– P0659 (boot), execute in the sense of a boot
0 ! 1
Boot
All of the parameters, which are not listed above, are appropriately pre–set (default)
standard values or are preset as a result of internal "calculate controller data" routine.
1
Standard state
The standard values are loaded. The motor code and power module code are write–
protected. The boot state can be re–established (with P0659 = 0).
2, 3, 4
Internal Siemens
1080
Calculate controller data
Using this function, suitable settings for the control parameters are calculated from the motor
parameters and several other parameters.
0 –>1
The controller data is being calculated, the function is active
0
Function inactive or exited error–free
Note:
S
Recommendation: Execute this function with SimoCom U, as the calculated parameters are
then displayed, and are only transferred and overwritten after acknowledgment.
S
At the end of the calculation, the parameter is automatically reset to 0 or a fault code is writ-
ten into it.
S
If there is an error condition, the parameters for current, flux and speed controller were not
able to be optimally pre–assigned. Standard values were entered.
The function can be re–started after the error cause has been removed.
Fault code:
–15
Magnetizing reactance (P1141) = 0
–16
Leakage reactance (P1139/P1140) = 0
–17
Rated motor frequency (P1134) = 0
–18
Rotor resistance (P1138) = 0
–19
Motor moment of inertia (P1117) = 0
–21
Speed at the start of field weakening (P1142) = 0
–22
Motor standstill current (P1118) = 0
–23
The ratio between the maximum motor current (P1104) and the motor standstill (stall)
current (P1118) is greater than the maximum value for the torque limit (P1230) and
the power limit (P1235)
–24
The ratio between the rated motor frequency (P1134) and the rated motor speed
(P1400) is not permissible (pole pair number)
4-132
Parameters
Name
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Min.
Standard
0
0
4
0
0
1
E Siemens AG 2005 All Rights Reserved
01.99
Max.
Units
Effective
PO
Immedi-
ately