01.99
Note
If P1146, P1147 or P1465 are changed during operation so that the set
limits are exceeded, then fault message 749 is output.
If the condition  is not violated, then when the system is
re–commissioned, the 14–bit resolution is preset and the speed actual
value smoothing (P1522) is selected.
If the resolver resolution is manually changed, then it is also necessary
to change the presetting of P1522 (refer to the parameter list
Attachment A.1).
Parameterizing
An indirect measuring system is commissioned by entering a code
indirect measuring
number into P1006. If an encoder is used which is not saved in the
systems
firmware, then the data according to Table 4-14 must be entered.
Refer to the parameter overview Chapter A.1 for the significance of
parameters P1005, P1021, P1022 and P1024.
Parameterizing a
For "SIMODRIVE 611 universal" when a direct measuring system is
direct measuring
used, it must be appropriately parameterized.
system
The direct measuring system is commissioned by entering a code num-
ber into P1036. If an encoder is used which is not saved in the firm-
ware, then the data according to Table 4-14 must be entered and
P1036 set to 99.
E Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
A Lists
A.4
Encoder list
A-889