A01251
CU: CU-EEPROM incorrect read-write data
Message class:
Hardware/software error (1)
Reaction:
NONE
Acknowledge:
NONE
Cause:
Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
For alarm value r2124 < 256, the following applies:
- carry out a POWER ON.
- replace the Control Unit.
For alarm value r2124 >= 256, the following applies:
- clear the fault memory (p0952 = 0).
- replace the Control Unit.
F01303
Component does not support the required function
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A function requested by the Control Unit is not supported by a DRIVE-CLiQ component.
Fault value (r0949, interpret decimal):
205: The Sensor Module does not support the selected temperature evaluation (r0458, r0459).
Remedy:
Upgrade the firmware of the DRIVE-CLiQ component involved.
A01304 (F)
Firmware version of DRIVE-CLiQ component is not up-to-date
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile memory has a more recent firmware version than the one in the connected DRIVE-CLiQ
component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component involved.
Remedy:
Update the firmware (p7828, p7829 and commissioning software).
A01306
Firmware of the DRIVE-CLiQ component being updated
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm automatically disappears after the firmware has been updated.
A01314
Topology: Component must not be present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "deactivate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1017