A01006
Firmware update for DRIVE-CLiQ component required
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The firmware of a DRIVE-CLiQ component must be updated as there is no suitable firmware or firmware version in
the component for operation with the Control Unit.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Firmware update using the commissioning software:
The firmware version of all of the components on the "Version overview" page can be read in the Project Navigator
under "Configuration" of the associated drive unit and an appropriate firmware update can be carried out.
Firmware update via parameter:
- take the component number from the alarm value and enter into p7828.
- start the firmware download with p7829 = 1.
A01007
POWER ON for DRIVE-CLiQ component required
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
A DRIVE-CLiQ component must be switched on again (POWER ON) (e.g. due to a firmware update).
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Note:
For a component number = 1, a POWER ON of the Control Unit is required.
Remedy:
- Switch off the power supply of the specified DRIVE-CLiQ component and switch it on again.
- For SINUMERIK, auto commissioning is prevented. In this case, a POWER ON is required for all components and
the auto commissioning must be restarted.
A01009 (N)
CU: Control module overtemperature
Message class:
Overtemperature of the electronic components (6)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The temperature (r0037[0]) of the control module (Control Unit) has exceeded the specified limit value.
Remedy:
- check the air intake for the Control Unit.
- check the Control Unit fan.
Note:
The alarm is automatically withdrawn once the limit value has been fallen below.
F01010
Drive type unknown
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An unknown drive type was found.
Remedy:
- replace Power Module.
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
F01015
Internal software error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1005