4 Faults and alarms
4.2 List of faults and alarms
Remedy:
- remove the corresponding component.
- change the setting "deactivate and not present".
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
A01315
Drive object not ready for operation
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the active drive object involved, at least one activated component is missing.
Note:
All other active and operational drive objects can be in the "RUN" state.
Remedy:
The alarm automatically disappears after the following action has been taken:
Re-insert the components involved.
A01316
Drive object inactive and again ready for operation
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
If, when inserting a component of the target topology, an inactive, non-operational drive object becomes operational
again.
Note:
This is the only message that is displayed for a de-activated drive object.
Remedy:
The alarm automatically disappears after the following action has been taken:
Again withdraw the component involved.
A01317 (N)
Deactivated component again present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
If a component of the target topology is inserted when a drive object is active.
Note:
This is the only message that is displayed for a deactivated component.
Remedy:
The alarm automatically disappears after the following action has been taken:
Again withdraw the component involved.
A01318
BICO: Deactivated interconnections present
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
This alarm is used in the following cases:
- if an inactive/non-operational drive object is active again/ready for operation
- if there are items in the list of BI/CI parameters (r9498[0...29], r9499[0...29])
- if the BICO interconnections saved in the list of BI/CI parameters (r9498[0...29], r9499[0...29]) have actually been
changed
Remedy:
Reset alarm:
- set p9496 to 1 or 2
or
- deactivate the drive object again.