Download Print this page

Siemens SINAMICS G120 List Manual page 1031

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

A01425
Topology: Serial number different
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component.
The serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = reserved
cc = number of differences (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- change over the actual topology to match the target topology.
- download the target topology that matches the actual topology (commissioning software).
For byte cc:
cc = 1 --> can be acknowledged using p9904 or p9905.
cc > 1 --> can be acknowledged using p9905 and can be deactivated using p9906 or p9907/p9908.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p9904 (Topology comparison acknowledge differences), p9905 (Device specialization)
A01428
Topology: Incorrect connection used
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component.
For a component, another connection was used.
The different connections of a component are described in the alarm value.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number of the target topology (%4)
cc = connection number of the actual topology (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- reinsert the DRIVE-CLiQ cable to the component (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p9904 (Topology comparison acknowledge differences)
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
4 Faults and alarms
4.2 List of faults and alarms
1031