8.6

PROFINET and PROFIBUS DP

Connecting interfaces for communication
Connect the communication interfaces of the SIMATIC Drive Controller using standardized
plug connectors.
Use preassembled connecting cables for the connection.
If you want to assemble the communication cables yourself, we recommend cables and RJ45
plug connectors from the Siemens FastConnect system.
Note
The X130 interface of the SIMATIC Drive Controller supports 10, 100 and 1000 Mbps.
For 1000 Mbps, you need 8-wire cables (4x2) and the 1000 Mbit version of the 180°
FastConnect connector.
The 145° FastConnect connectors can only be used for Ethernet interface X130 with a max.
of 100 Mbps.
8.7

Digital inputs and digital inputs/outputs X122, X132 and X142

The digital inputs and digital inputs/outputs at interfaces X122, X132 and X142 are designed
for the connection of sensors and actuators.
The digital inputs and digital inputs/outputs at X122 and X132 interfaces are assigned to
SINAMICS Integrated. Through configuration (frames 39x), you can also use the digital inputs
and digital outputs (X122/X132) for the CPU.
The digital input/outputs at interface X142 are assigned to the CPU of the SIMATIC Drive
Controller and that assignment is fixed.
Using the digital inputs and digital outputs
Digital inputs/digital outputs come in the following types:
• Digital inputs (DI)
• Bidirectional digital inputs/outputs (DI/DQ)
Bidirectional digital input/outputs can be configured channel-by-channel as digital input or
digital output.
SIMATIC Drive Controller
System Manual, 11/2023, A5E46600094-AD
Connecting
8.6 PROFINET and PROFIBUS DP