STO (Menu Index 7.3)
6.8.4
P 7.3.1 Safe Torque Off Response
Description: Select the response of the drive to the activation of Safe Torque Off.
Default Value: 14 [Fault]
Unit: -
The following are the selections for the parameter.
Selection Number
15
14
P 7.3.2 Safe Torque Off Output
Description: Select an output for signaling the activation of Safe Torque Off.
Default Value:
Unit: -
Terminating STO and Resuming Normal Operation
6.8.5
1.
Reapply 24 V DC supply to STO inputs.
2.
Give a reset signal (via bus, digital 1/0, or the control panel).
Set the STO function to restart automatically by setting the default value in parameter 7.2.1 Safe Torque Off Reaction. This
way, STO is terminated and normal operation is resumed, when the 24 V DC is applied to STO inputs. No reset signal is
required.
Customization (Menu Index 8)
6.9
Customization Overview
6.9.1
This parameter group contains parameters for customizing and adapting the behavior of the drive and user interface design.
Basic Settings (Menu Index 8.2)
6.9.2
P 8.2.1 Date and Time
Description: Set the actual time and date. Format is YYYY-MM-DD and HH:MM:SS.
Default Value:
Unit: -
© 2023.11
Parameter Type: Selection
Data Type: UINT
Selection Name
Warning
Fault
Parameter Type: Selection
Data Type: UINT
Parameter Type: Range (\* — \*)
Data Type: DATE_AND_TIME
Parameter Number: 9910
Access Type: Read/Write
Selection Description
The drive issues a warning.
The drive issues a fault and coasts the
motor.
Parameter Number: 9911
Access Type: Read/Write
Parameter Number: 2800
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |
303