Application Guide | iC7 Series Motion
Description: Select the unit voltage class to optimize the performance of the drive.
Default Value: \*
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
3
P 2.2.1.2 Overload Mode
Description: Select the overload mode.
Default Value: \*
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
2
3
P 2.2.1.3 Relative Output Current Limit
Description: Set the output current limit relative to the motor nominal current from the nameplate.
Default Value: 150
Unit: %
P 2.2.1.5 Supply Mode
104
| © 2023.11
Parameter Type: Selection
Data Type: UINT
Selection Name
Low-voltage range
Mid-voltage range
High-voltage range
Parameter Type: Selection
Data Type: UINT
Selection Name
Automatic
Low overload (LO)
High overload (HO1)
High overload increased duty (HO2)
Parameter Type: Range (0 — 200)
Data Type: REAL
Parameter Number: 2832
Access Type: Read/Conditional Write
Selection Description
Class 1 - Low-voltage range.
Class 2 - Mid-voltage range.
Class 3 - High-voltage range.
Parameter Number: 2833
Access Type: Read/Conditional Write
Selection Description
Combination of high and low overload.
Drive will start at high overload, but
switches to low overload for a period at
too high load.
Low overload (LO) operation. Provides
overload current up to 110%.
High overload (HO1) operation. Provides
higher overload current up to 160% for
acceleration.
High overload with increaseed duty (HO2)
operation. Provides higher overload
current with shorter cycle times.
Parameter Number: 1325
Access Type: Read/Write
AB318753549016en-000301 / 136R0284