Application Guide | iC7 Series Motion
Default Value:
Unit: -
P 3.4.3 Thermal Switch Response
Description: Select which function is activated if the thermal input indicates too high a temperature.
Default Value: 1 [Fault, ramp to coast]
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
P 3.4.4 Thermal Switch Input
Description: Select the digital input terminal for the thermal switch.
Default Value:
Unit: -
P 3.4.5 Power Stabilizer Gain
Description: Set the controller gain for power stabilization. The power stabilizer dampens possible resonance with the grid. If set to -1
the value is selected automatically, if set to 0 the controller is disabled.
Default Value: -1
Unit: %
P 3.4.6 Power Stabilizer Bandwidth
Description: Set the controller bandwidth for power stabilization.
Default Value: 100
Unit: %
Output Filter (Menu Index 3.5)
6.4.7
P 3.5.1 Output Filter Type
Description: Select the output filter type.
122
| © 2023.11
Parameter Type: Selection
Data Type: UINT
Parameter Type: Selection
Data Type: UINT
Selection Name
Fault, ramp to coast
Derate
Parameter Type: Selection
Data Type: UINT
Parameter Type: Range (-1 — 500)
Data Type: REAL
Parameter Type: Range (1 — 10000)
Data Type: REAL
Parameter Number: 3412
Access Type: Read/Write
Parameter Number: 3413
Access Type: Read/Write
Selection Description
Issues a fault, ramps down, and coast.
The drive issues a fault, continues
operation, and derates to protect the filter.
Parameter Number: 3414
Access Type: Read/Write
Parameter Number: 3415
Access Type: Read/Write
Parameter Number: 3416
Access Type: Read/Write
AB318753549016en-000301 / 136R0284