Danfoss iC7 Motion Series Application Manual page 173

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
Description: Enable faults to be reset from all control places.
Default Value: 1 [Enabled]
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
P 5.5.2.9 Alternative Control Place Selection
Description: Select the alternative control place.
Default Value: 4 [Advanced control]
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
3
4
P 5.5.2.10 Alternative Control Place Input
Description: Select the digital input terminal for activating the alternative control place.
Default Value:
Unit: -
Local Control (Menu Index 5.5.3)
6.6.7.4
Settings (Menu Index 5.5.3.1)
6.6.7.4.1
P 5.5.3.1.1 Allow Local Control Force Stop
Description: Select whether the control panel stop button always stops the drive, regardless of the selected control place. Pressing the
stop button also places the drive in local control.
© 2023.11
Parameter Type: Selection
Data Type: BOOL
Selection Name
Disabled
Enabled
Parameter Type: Selection
Data Type: UINT
Selection Name
Local control
Fieldbus control
I/O control
Advanced control
Parameter Type: Selection
Data Type: UINT
Parameter Number: 109
Access Type: Read/Write
Selection Description
Disables the function.
Enables the function.
Parameter Number: 115
Access Type: Read/Write
Selection Description
The drive is controlled by a connected
control panel.
The drive is controlled via a fieldbus.
The drive is controlled via I/O.
The drive is controlled via a combination
of I/O and fieldbus.
Parameter Number: 111
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |
171