Danfoss iC7 Motion Series Application Manual page 109

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
P 2.2.1.16 Power Limit Motor Delay
Description: Set the delay before the selected response is triggered after the drive has reached the power limit.
Default Value:
Unit: s
P 2.2.1.17 Power Limit Generator Response
Description: Select the response for running within power limit after the time delay set.
Default Value: 0 [No response]
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
10
P 2.2.1.18 Power Limit Generator Delay
Description: Set the delay before the selected response is triggered after the drive has reached the power limit.
Default Value:
Unit: s
Additional Information for Power Unit General Settings
6.3.3.2
P 2.2.1.1 Unit Voltage Class
This parameter specifies a focused voltage range within the input voltage rating of the power unit, for optimized drive control. Each
power unit is rated for a wide input voltage range within which the drive can operate. This parameter is used to specify a narrower
range within the wide range of input voltage, to determine optimized values for the nominal voltage and current of the power unit. The
following table describes the selections available for the parameter.
© 2023.11
Parameter Type: Range (0 — 65000)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Selection Name
No response
Info
Fault
Parameter Type: Range (0 — 65000)
Data Type: REAL
Parameter Number: 2364
Access Type: Read/Write
Parameter Number: 2367
Access Type: Read/Write
Selection Description
The event is ignored.
The event is logged in the event log.
The drive issues a fault and coasts the
motor.
Parameter Number: 2365
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |