Application Guide | iC7 Series Motion
Selection Number
0
1
2
P 3.2.2 Brake Chopper Voltage Reduce
Description: Set the activation level of the brake chopper. If set to 0, the brake chopper is active if the voltage exceeds the overvoltage
control activation level. The value set is subtracted from the overvoltage control activation level, lowering the brake chopper activation
level, respectively.
Default Value: 0
Unit: V
Brake Resistor (Menu Index 3.3)
6.4.4
P 3.3.1 Brake Resistor Test
Description: Enables the brake resistor test. The drive conducts a test of brake resistor presence while the drive is coasted. Starting of the
drive is prohibited until the test is completed.
Default Value: NA
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
P 3.3.2 Brake Resistor Resistance
Description: Set the resistance value of the brake resistor.
Default Value: 5
Unit: Ω
P 3.3.3 Brake Resistor Power Limit
Description: Set the power limit for resistor braking.
120
| © 2023.11
Selection Name
Disabled
Enabled in Run and Coast
Enabled in run only
Parameter Type: Range (0 — 50)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Selection Name
Off
Enable brake chopper test run
Parameter Type: Range (\* — \*)
Data Type: REAL
Selection Description
Enables the brake chopper both while
running and at coast.
Enables the brake chopper while running.
Parameter Number: 2938
Access Type: Read/Write
Parameter Number: 430
Access Type: Read/Conditional Write
Selection Description
Executes a test of the brake chopper
and brake resistor to check if they are
operational.
Parameter Number: 2936
Access Type: Read/Conditional Write
AB318753549016en-000301 / 136R0284