Selection Number
0
1
References (Menu Index 5.5.6.2)
6.6.7.7.2
P 5.5.6.2.1 Adv. Speed Reference
Description: Select the speed reference sources for when the drive operates in advanced control. Select 2 sources to combine them into
1 reference value.
Default Value: [2,3]
Unit: -
The following are the selections for the parameter.
Selection Number
0
2
3
4
5
P 5.5.6.2.2 Adv. Speed Reference Logic
Description: Select how to form the speed reference out of the 2 sources when operating in advanced control.
Default Value: 2 [Sum]
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
2
3
4
5
© 2023.11
Selection Name
Disabled
Enabled
Parameter Type: Selection
Data Type: UINT
Selection Name
None
Fieldbus reference
Reference 1 input
Reference 2 input
Preset reference
Parameter Type: Selection
Data Type: UINT
Selection Name
Source 1
Source 2
Sum
Subtract
Divide
Multiply
Selection Description
Disables the function.
Enables the function.
Parameter Number: 1915
Access Type: Read/Write
Selection Description
No source selected equals a 0 value.
Use reference from the fieldbus.
Use the reference from I/O reference 1.
Use the reference from I/O reference 2.
Use reference from the preset reference.
Parameter Number: 1916
Access Type: Read/Write
Selection Description
Use value from source 1 only.
Use value from source 2 only.
Add references from source 1 and 2
together.
Subtract source 2 from source 1.
Divide source 1 with source 2.
Multiply source 1 with source 2.
AB318753549016en-000301 / 136R0284 |