Application Guide | iC7 Series Motion
Selection Number
0
6
P 9.5.2.2 T33 Terminal Type
Description: Select the type of the terminal. If voltage is selected, the unit is V. If current is selected, the unit is mA.
Default Value: 1 [Voltage]
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
P 9.5.2.3 T33 Minimum Value
Description: Set the voltage or current representing 0% of the signal.
Default Value: 0
Unit: -
P 9.5.2.4 T33 Maximum Value
Description: Set the voltage or current representing 100% of the signal.
Default Value: 10
Unit: -
P 9.5.2.5 T33 Filter Time
Description: Set the filter time for the terminal.
Default Value: 0.00
Unit: ms
P 9.5.2.6 T33 Live Zero Threshold Value
Description: Set the live zero threshold value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2 Live
Zero Response".
342
| © 2023.11
Selection Name
Inactive
Analog Input
Parameter Type: Selection
Data Type: UINT
Selection Name
Voltage
Current
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (0.00 — 60000.00)
Data Type: REAL
Selection Description
Configures the terminal as analog input.
Parameter Number: 2273
Access Type: Read/Write
Selection Description
Terminal set to voltage mode.
Terminal set to current mode.
Parameter Number: 2272
Access Type: Read/Write
Parameter Number: 2271
Access Type: Read/Write
Parameter Number: 2270
Access Type: Read/Write
AB318753549016en-000301 / 136R0284