Application Guide | iC7 Series Motion
Selection Number
6
9
10
P 10.3.1.13 Process Data Timeout Control Place
Description: Select the alternative control place to be used in case of filedbus timeout. This is only valid in case of timeout warning or
info.
Default Value: 1 [Local control]
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
3
4
PROFINET (Menu Index 10.3.2)
6.11.3.2
Configuration (Menu Index 10.3.2.2)
6.11.3.2.1
P 10.3.2.2.1 Name of Station
Description: Set the name of station. The PROFINET device is identified by its name of station. Each name must be unique in the
network.
Default Value:
Unit: -
Diagnosis (Menu Index 10.3.2.3)
6.11.3.2.2
P 10.3.2.3.1 Diagnostic Fault
© 2023.11
Selection Name
Warning - Change Control Place -
Persistent
Fault, ramp to coast
Fault
Parameter Type: Selection
Data Type: UINT
Selection Name
Local control
Fieldbus control
I/O control
Advanced control
Parameter Type: Range (\* — \*)
Data Type: STRING
Selection Description
The drive issues a warning, and the
control place changes to the selected
alternative while the timeout warning
is active. The control place requires a
reset command to change back to the
original one after the fieldbus process
data returns.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the
motor.
Parameter Number: 112
Access Type: Read/Write
Selection Description
The drive is controlled by a connected
control panel.
The drive is controlled via a fieldbus.
The drive is controlled via I/O.
The drive is controlled via a combination
of I/O and fieldbus.
Parameter Number: 7080
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |
351