Danfoss iC7 Motion Series Application Manual page 345

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
Default Value: -10
Unit: -
P 9.5.2.7 T33 Live Zero Timeout Value
Description: Set the live zero timeout value for the terminal. The response to a live zero event is defined with parameter "5.2.15.2 Live
Zero Response".
Default Value: 0.0
Unit: s
Input T34 (Menu Index 9.5.3)
6.10.2.4.3
P 9.5.3.1 T34 Terminal Mode
Description: Select the mode for the terminal.
Default Value: 6 [Analog Input]
Unit: -
The following are the selections for the parameter.
Selection Number
0
6
7
P 9.5.3.2 T34 Terminal Type
Description: Select the type of the terminal. If voltage is selected, the unit is V. If current is selected, the unit is mA.
Default Value: 1 [Voltage]
Unit: -
The following are the selections for the parameter.
Selection Number
1
2
P 9.5.3.3 T34 Minimum Value
Description: Set the voltage or current representing 0% of the signal.
© 2023.11
Parameter Type: Range (-20 — 20)
Data Type: REAL
Parameter Type: Range (0.0 — 60.0)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Selection Name
Inactive
Analog Input
Temperature input
Parameter Type: Selection
Data Type: UINT
Selection Name
Voltage
Current
Parameter Number: 2274
Access Type: Read/Write
Parameter Number: 2275
Access Type: Read/Write
Parameter Number: 2021
Access Type: Read/Write
Selection Description
Configures the terminal as analog input.
Configures the terminal as temperature
sensor input.
Parameter Number: 2279
Access Type: Read/Write
Selection Description
Terminal set to voltage mode.
Terminal set to current mode.
AB318753549016en-000301 / 136R0284 |
343