Application Guide | iC7 Series Motion
Default Value: 0.03
Unit: Ω
P 4.2.3.6 Magnetizing Reactance Xm
Description: Set the motor magnetizing reactance. Overwritten by AMA.
Default Value: 0.94
Unit: Ω
Additional Information for Induction Motor
6.5.3.6
P 4.2.3.2 Rotor Resistance Rr
Use any of the following methods for setting Rr:
Run an AMA on a cold motor. The drive measures the value from the motor. All compensations are reset to 100%.
l
Enter the Rr value manually. Obtain the value from the motor supplier.
l
Use the Rr default setting. The drive establishes the setting based on the motor nameplate data.
l
P 4.2.3.3 Iron Loss Resistance Rfe
The RFe value cannot be found by performing an AMA. The RFe value is especially important in torque control applications. If RFe is
unknown, make sure to keep the default setting of the parameter.
P 4.2.3.4 Stator Leakage Reactance Xls
Use any of the following methods for setting Xls:
Run an AMA on a cold motor. The drive measures the value from the motor.
l
Enter the Xls value manually. Obtain the value from the motor supplier.
l
Use the Xls default setting. The drive establishes the setting based on the motor nameplate data.
l
P 4.2.3.5 Rotor Leakage Reactance Xlr
Use any of the following methods to set Xlr:
Run an AMA on a cold motor. The drive measures the value from the motor.
l
Enter the Xlr value manually. Obtain the value from the motor supplier.
l
Use the Xlr default setting. The drive establishes the setting based on the motor nameplate data.
l
Permanent Magnet Motor (Menu Index 4.2.4)
6.5.3.7
P 4.2.4.1 Back EMF
Description: Set the stator nominal induced voltage (back-EMF voltage) when running at 1000 RPM (line-to-line RMS). Overwritten by
AMA.
Default Value: 190
Unit: V
P 4.2.4.2 Stator Resistance Rs
Description: Set the motor stator resistance. Overwritten by AMA.
© 2023.11
Parameter Type: Range (0.00 — 62.83)
Data Type: REAL
Parameter Type: Range (0.00 — 62.83)
Data Type: REAL
Parameter Type: Range (0 — 10000)
Data Type: REAL
Parameter Number: 441
Access Type: Read/Conditional Write
Parameter Number: 442
Access Type: Read/Conditional Write
Parameter Number: 415
Access Type: Read/Conditional Write
AB318753549016en-000301 / 136R0284 |
133