Application Guide | iC7 Series Motion
Default Value: 100
Unit: %
P 2.3.2.4 Overvoltage Control Td
Description: Set the scaling of the overvoltage control derivation time.
Default Value: 100
Unit: %
P 2.3.2.5 Overvoltage Control Upper limit
Description: Set the upper limit for the overvoltage control. However, the voltage can be limited internally by the drive because of the
available hardware, temperature, and time.
Default Value: 796.5
Unit: V
Additional Information for Overvoltage Protection
6.3.4.4
P 2.3.2.1 Overvoltage Control
Table 39: Selection Descriptions
Selection name
Disable
Enable
Power Loss (Menu Index 2.3.3)
6.3.4.5
P 2.3.3.3 Power Loss Response
Description: Select the response to an insufficient supply voltage.
Default Value: 1 [Undervoltage control]
Unit: -
The following are the selections for the parameter.
© 2023.11
Parameter Type: Range (0 — 10000)
Data Type: REAL
Parameter Type: Range (0 — 10000)
Data Type: REAL
Parameter Type: Range (\* — \*)
Data Type: REAL
Selection description
• The overvoltage controller does not affect motor speed in any manner.
• DC-link voltage is controlled with a brake chopper.
Note:
A DC-link overvoltage fault is usually triggered when the DC-link voltage exceeds
acceptable levels.
When the DC-link voltage level exceeds the overvoltage level, motor speed or deceleration is lim-
ited by the controller.
Parameter Type: Selection
Data Type: UINT
Parameter Number: 1804
Access Type: Read/Write
Parameter Number: 1805
Access Type: Read/Write
Parameter Number: 1816
Access Type: Read/Write
Parameter Number: 1818
Access Type: Read/Conditional Write
AB318753549016en-000301 / 136R0284 |
115