Danfoss iC7 Motion Series Application Manual page 161

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
Default Value: 120
Unit: °C
P 5.2.3.4.3 Temp. 3 Limit 2
Description: Set the temperature level for issuing a protection response.
Default Value: 150
Unit: °C
P 5.2.3.4.4 Temp. 3 Limit 2 Response
Description: Select the response for exceeding the limit.
Default Value: 9 [Fault, ramp to coast]
Unit: -
The following are the selections for the parameter.
Selection Number
3
9
10
Temp. 4 Protection (Menu Index 5.2.3.5)
6.6.4.4.5
P 5.2.3.5.1 Temp. 4 Input
Description: Select the temperature sensor input for the temperature protection.
Default Value:
Unit: -
P 5.2.3.5.2 Temp. 4 Limit 1
Description: Set the temperature level for issuing a warning.
Default Value: 120
Unit: °C
P 5.2.3.5.3 Temp. 4 Limit 2
Description: Set the temperature level for issuing a protection response.
© 2023.11
Parameter Type: Range (-300 — 300)
Data Type: REAL
Parameter Type: Range (-300 — 300)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Selection Name
Warning
Fault, ramp to coast
Fault
Parameter Type: Selection
Data Type: UINT
Parameter Type: Range (-300 — 300)
Data Type: REAL
Parameter Number: 5215
Access Type: Read/Write
Parameter Number: 5216
Access Type: Read/Write
Parameter Number: 5217
Access Type: Read/Write
Selection Description
The drive issues a warning.
Issues a fault, ramps down, and coast.
The drive issues a fault and coasts the
motor.
Parameter Number: 5218
Access Type: Read/Write
Parameter Number: 5219
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |