Application Guide | iC7 Series Motion
Description: Set the output phase sequence. This function virtually swaps the output phases, which can be used to change the direction
of motor rotation without having to physically rewire motor cables.
Default Value: 0 [UVW]
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
Additional Information for Motor Data General Settings
6.5.3.2
P 4.2.1.2 Number of Pole Pairs
The synchronous speed of a motor can be calculated when the supply frequency and number of pole pairs are known. The formula to
calculate the synchronous speed of the motor (ns) with supply frequency (f ) and number of pole pairs (p) is as follows:
A
Figure 72: Two Inductors in 1 Phase Connected in Series to A) 2 Poles B) 4 Poles
While the frequency is determined by the grid or the AC drive, the number of poles is determined by the way the stator inductors are
connected. Pole pairs (p) or pole number and synchronous motor speed lists the number of poles corresponding to synchronous speed
(n0) at 50 Hz and 60 Hz supply.
Table 43: Number of Pole Pairs (p) and Nominal Speed (~nn) for Motors @ 50 Hz and 60 Hz
Number of pole pairs (p)
1
2
3
© 2023.11
Parameter Type: Selection
Data Type: UINT
Selection Name
UVW
WVU
B
Parameter Number: 431
Access Type: Read/Conditional Write
Selection Description
Select the normal phase sequence.
Select the reverse phase sequence.
~nn @ 50 Hz
~nn @ 60 Hz
2700–2880
3250–3460
1350–1450
1625–1730
700–960
840–1153
AB318753549016en-000301 / 136R0284 |
129