Danfoss iC7 Motion Series Application Manual page 215

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
Selection Number
0
1
2
Speed Ramps (Menu Index 5.8.6)
6.6.10.9
Speed Ramps Overview
6.6.10.9.1
Ramps are used for reaching the desired speed reference in a controlled manner. The parameters in the Speed Ramps parameter group is
used to select the ramp type and to adjust their shapes.
Ramps 1–4 can be configured as linear or S-ramps. A linear ramp provides the motor a constant acceleration. The S-ramp allows the drive
to compensate for jerk in the application and/or to reduce sway.
The following diagram illustrates how the ramp parameters are used for adjusting the ramp profiles.
Speed
(3)
(4)
(1)
Figure 84: Speed Ramps
1
Ramp acceleration time
3
Ramp acceleration increase time for S-ramps
5
Ramp deceleration increase time for S-ramps
Furthermore, the drive supports a variable ramp profile, which allows the changing of the acceleration and deceleration time
dynamically with analog inputs.
Speed Ramp Settings (Menu Index 5.8.6.1)
6.6.10.9.2
P 5.8.6.1.1 Ramp Selector
Description: Select the speed ramp.
Default Value: 0 [Ramp 1]
Unit: -
The following are the selections for the parameter.
© 2023.11
Selection Name
Step and Ramp
Ramp
Step
Time
(5)
(6)
(2)
Parameter Type: Selection
Data Type: UINT
Selection Description
Step increment and ramp thereafter.
Ramp increment.
Step increment.
2
Ramp deceleration time
4
Ramp acceleration decrease time for S-ramps
6
Ramp deceleration decrease time for S-ramps
Parameter Number: 1100
Access Type: Read/Write
AB318753549016en-000301 / 136R0284 |
213