Application Guide | iC7 Series Motion
Default Value: 100
Unit: %
Speed Limits and Monitor (Menu Index 5.8.3)
6.6.10.5
P 5.8.3.1 Positive Speed Limit
Description: Set the speed limit for positive direction.
Default Value: 50
Unit: Hz
P 5.8.3.2 Negative Speed Limit
Description: Set the speed limit for negative direction.
Default Value: -50
Unit: Hz
P 5.8.3.3 Minimum Speed Limit
Description: Set the minimum speed for positive and negative direction.
Default Value: 0
Unit: Hz
P 5.8.3.4 High Speed Warning
Description: Set the speed value which activates the high speed warning. Activated after 1 s.
Default Value: 1000
Unit: Hz
P 5.8.3.5 High Speed Fault
Description: Set the speed value which activates the high speed fault after a delay.
Default Value: 1000
Unit: Hz
P 5.8.3.6 High Speed Fault Delay
Description: Set the delay time after which a fault is issued if the speed set for high speed fault is exceeded.
Default Value: 10
Unit: s
206
| © 2023.11
Parameter Type: Range (0 — 1000)
Data Type: REAL
Parameter Type: Range (0 — 1000)
Data Type: REAL
Parameter Type: Range (-1000 — 0)
Data Type: REAL
Parameter Type: Range (\* — \*)
Data Type: REAL
Parameter Type: Range (0 — 10000)
Data Type: REAL
Parameter Type: Range (0 — 1000)
Data Type: REAL
Parameter Type: Range (0 — 360)
Data Type: UDINT
Parameter Number: 5434
Access Type: Read/Write
Parameter Number: 1729
Access Type: Read/Write
Parameter Number: 1728
Access Type: Read/Write
Parameter Number: 1722
Access Type: Read/Write
Parameter Number: 1200
Access Type: Read/Write
Parameter Number: 1201
Access Type: Read/Write
Parameter Number: 1202
Access Type: Read/Write