Danfoss iC7 Motion Series Application Manual page 234

Hide thumbs Also See for iC7 Motion Series:
Table of Contents

Advertisement

Application Guide | iC7 Series Motion
P 5.9.2.35 Regenerative Torque Limit Response
Description: Select the response for running in regenerative torque limit after the time delay defined.
Default Value: 0 [No response]
Unit: -
The following are the selections for the parameter.
Selection Number
0
1
10
P 5.9.2.36 Regenerative Torque Limit Delay
Description: Set the delay the drive is allowed to be in regenerative torque limit before a response is issued.
Default Value:
Unit: s
Torque Reference (Menu Index 5.9.3)
6.6.11.4
P 5.9.3.1 Torque Reference 1 Input
Description: Select the input terminal or a predefined fixed value for the torque reference.
Default Value:
Unit: -
P 5.9.3.2 Torque Reference 2 Input
Description: Select the input terminal or a predefined fixed value for the torque reference.
Default Value:
Unit: -
P 5.9.3.3 Torque Reference 1 Max.
Description: Set the maximum torque reference value in % of nominal motor torque.
Default Value: 100
Unit: %
232
| © 2023.11
Parameter Type: Selection
Data Type: UINT
Selection Name
No response
Info
Fault
Parameter Type: Range (0 — 65000)
Data Type: REAL
Parameter Type: Selection
Data Type: UINT
Parameter Type: Selection
Data Type: UINT
Parameter Type: Range (-300 — 300)
Data Type: REAL
Parameter Number: 2362
Access Type: Read/Write
Selection Description
The event is ignored.
The event is logged in the event log.
The drive issues a fault and coasts the
motor.
Parameter Number: 2363
Access Type: Read/Write
Parameter Number: 4534
Access Type: Read/Write
Parameter Number: 4535
Access Type: Read/Write
Parameter Number: 4530
Access Type: Read/Write