4.7 Auto-Tuning
NOTICE: Never perform Rotational Auto-Tuning for a motor connected to a load. Failure to comply could result in improper drive operation.
If Rotational Auto-Tuning is performed for a motor coupled to a load, the motor parameters will be inaccurate and the motor may exhibit
abnormal operation. Disconnect or decouple the motor from the load.
Enter the required information from the motor nameplate. Press
Note:
These instructions continue from Step 7 in "Enter Data from the Motor Nameplate".
After setting T1-07 as illustrated in the previous section, press
1.
display is as described below:
Press
to activate Auto-Tuning.
2.
Note: The first digit indicates which motor is undergoing Auto-Tuning (motor 1 or motor
2). The second digit indicates the type of Auto-Tuning being performed.
3.
Auto-Tuning finishes in approximately one to two minutes.
u

Input Data for Auto-Tuning

The T1-oo parameters are used to set the Auto-Tuning input data.
Note:
1. Cycling power to the drive will reset any values set during the Auto-Tuning process to factory defaults.
2. For motors that are to be operated in the field weakening range, first perform the Auto-Tuning with the base data, i.e. the frequency at
which the motor is operating with its rated voltage (base frequency). After Auto-Tuning is complete, change the maximum frequency
E1-04 to the desired value.
n
T1-00: Motor 1/Motor 2 Selection
Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input is set for function H1-oo = 16. This
parameter is not displayed if motor 1/2 switching is disabled.
No.
T1-00
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E1-oo and E2-oo for motor 1.
Setting 2: Motor 2
Auto-Tuning automatically sets parameters E3-oo and E4-oo for motor 2. Make sure that motor 2 is connected to the drive
for Auto-Tuning.
n
T1-01: Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
Tuning.
No.
T1-01
Setting 0: Rotating Auto-Tuning for Open Loop Vector Control
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotating Auto-Tuning for V/f Control
n
T1-02: Motor Rated Power
Used to set the motor rated power according to the motor nameplate value. For optimal performance, the motor rated power
should be between 50 and 100% of the drive rating.
No.
T1-02
<1> The setting range differs based on drive software version.
PRG: 1016 and later: 0.03 to 650.00 kW
106
Step
flashes.
Name
Motor 1/2 Selection
Refer to Types of Auto-Tuning on page 102
Name
Auto-Tuning Mode Selection
Name
Motor Rated Power
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
to proceed to the Auto-Tuning start display.
and confirm the
Setting Range
for details on different types of Auto-
Setting Range
0, 2 (OLV) 2, 3 (V/f)
Setting Range
Display/Result
Default
1 or 2
Default
0 (OLV) 2 (V/f)
Default
Determined by
<1>
o2-04 and C6-01