NTP-G2 Install the Shelf Assembly
NTP-G2 Install the Shelf Assembly
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be bolted to the
Warning
floor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip
over. Statement 1048
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations. Statement 1045
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
Warning
recommended ambient temperature of:
45°C (113°F). Statement 1047
Warning
Take care when connecting units to the supply circuit so that wiring is not overloaded. Statement 1018
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
1-8
This procedure reverses the mounting bracket and mounts shelf assemblies
in a rack.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Pinned hex tool
ETSI only:
Two M6 x 20 socket set screws
Eight M6 x 20 pan-head Phillips mounting screws
ANSI only:
Two #12-24 x 3/4 set screws (48-1003-XX)
Eight #12-24 x 3/4 pan-head Phillips mounting screws (48-1004-XX,
48-1007-XX)
NTP-G1 Unpack and Inspect the Shelf Assembly, page 1-6
Required
Onsite
None
Chapter 1
Install the Shelf and Common Control Cards
August 2005