Chapter 3
Turn Up a Node
Figure 3-19
Rear View of the Patch Panel
.
DEMUX connectors (TX port [drop] from the 32DMX or 32DMX-O cards)
MUX connectors (RX port [add] to the 32WSS or 32MUX-O cards)
Figure 3-20
Top View of the Patch-Panel Bar
CLIENT
Step 9
As necessary, repeat Steps
MUX-O card, until all 32 connectors on the bottom row of the rear of the patch panel are connected.
At the adjacent 32DMX or DMX-O card in that side of the shelf, plug the MPO connector of an MPO
Step 10
cable into the top ADD RX (30.3 -36.6) port of the 32DMX or DMX-O card. If you are connecting to
the next MPO cable, plug it into the MPO connector below the previous MPO cable.
Route the MPO cable slack through the patch-panel tray as necessary.
Step 11
When you close the patch-panel tray, the cables must not be pinched, and the cable bend radius must be
Caution
equal to or greater than the minimum radius that is recommended in your site specifications. As you
route each cable through the patch-panel tray, make sure that adequate cable slack remains.
While facing the front of the patch panel, at the rear of the patch panel, plug the eight LC-connector
Step 12
fan-out cables on the MPO cable into their corresponding connectors on the top row of the patch panel.
You should plug the fan-out cables from left to right (as you face the patch panel), following the numbers
tagged (1 through 8) on the cables.
As necessary, repeat Steps
Step 13
all 24 connectors on the top row of the rear of the patch panel are connected.
For a hub or ROADM node, repeat Steps
Step 14
patch panel. For a terminal node, go to Step 15.
Return to your originating procedure (NTP).
Step 15
September 2005
DLP-G315 Install Fiber-Optic Cables From the 32WSS/32DMX and 32MUX-O/32DMX-O Cards to the Patch Panel
CLIENT
6
through
8
10
through
12
CLIENT
for the remaining three Add Rx ports on the 32WSS or
for the remaining three Add Rx ports on the 32DMX card, until
5
through
13
to cable the other side of the shelf to the second
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
CLIENT
3-77