Figure 1-15 Cisco Ons 15454 Power Terminals - Cisco ONS 15454 DWDM Installation And Operation Manual

Hide thumbs Also See for ONS 15454 DWDM:
Table of Contents

Advertisement

DLP-G18 Connect Office Power to the ONS 15454 ANSI
Figure 1-15
Return leads (black)
Remove or loosen the #8 power terminal screws on the ONS 15454. To avoid confusion, label the cables
Step 4
connected to the BAT1/RET1 (A) power terminals as 1, and the cables connected to the BAT2/RET2
(B) power terminals as 2.
Note
Before you make any crimp connections, coat all bare conductors (battery, battery return, and frame
Caution
ground) with an appropriate antioxidant compound. Bring all unplated connectors, braided strap, and bus
bars to a bright finish, then coat with an antioxidant before you connect them. You do not need to prepare
tinned, solder-plated, or silver-plated connectors and other plated connection surfaces, but always keep
them clean and free of contaminants.
Caution
When terminating power, return, and frame ground, do not use soldering lug, screwless (push-in)
connectors, quick-connect, or other friction-fit connectors.
Strip 1/2 inch (12.7 mm) of insulation from all power cables that you will use.
Step 5
Crimp the lugs onto the ends of all power leads.
Step 6
Note
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
1-38
Cisco ONS 15454 Power Terminals
RET 1
BAT 1
CAUTION: Remove power from both
the BAT1 and terminal blocks
prior to servicing
Use only pressure terminal connectors, such as ring and fork types, when terminating the battery,
battery return, and frame ground conductors.
When terminating battery and battery return connections as shown in
torque specification of 10 in-lb.
Chapter 1
Battery leads (red)
RET 2
BAT 2
-42 V
24 A
SUITABLE FOR MOUNTING ON
A NON-COMBUSTIBLE SURFACE.
PLEASE REFER TO INSTALLATION
INSTRUCTIONS.
Install the Shelf and Common Control Cards
Figure
1-15, follow a
August 2005