NTP-G11 Install an External Wire-Wrap Panel on the AEP (ANSI Only)
Wrap the ground wire of your computer cable to pin A3 on the craft pin field.
assignments for the CRAFT pin field.
Note
Table 1-8
Pin Field
Craft
Return to your originating procedure (NTP).
Step 3
NTP-G11 Install an External Wire-Wrap Panel on the AEP
(ANSI Only)
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Position the lower cover over the AEP. Make sure that the AEP AMP Champ connectors protrude
Step 1
through the cutouts in the lower cover
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
1-58
You cannot use the craft backplane pins and the EIA/TIA-232 port on the TCC2/TCC2P card
simultaneously. Using a combination prevents access to the node or causes a loss in connectivity.
Craft Interface Pin Assignments
Contact
Function
A1
Receive
A2
Transmit
A3
Ground
A4
DTR
This procedure connects an external wire-wrap panel to the ONS 15454
ANSI AEP to provide the physical alarm contacts for the AEP.
External wire-wrap panel
NTP-G9 Install the Alarm Expansion Panel (ANSI Only), page 1-44
As needed
Onsite
None
Chapter 1
(Figure
1-23).
Install the Shelf and Common Control Cards
Table 1-8
shows the pin
August 2005