DLP-G315 Install Fiber-Optic Cables From the 32WSS/32DMX and 32MUX-O/32DMX-O Cards to the Patch Panel
Figure 3-18
MPO Cable
.
To the Add/Drop port
n a 32WSS, 40-WSS-C,
or 32-MUX-O card
Step 7
Route the MPO cable slack through the patch-panel tray as necessary.
When you close the patch-panel tray, the cables must not be pinched, and the cable bend radius must be
Caution
equal to or greater than the minimum radius that is recommended in your site specifications. As you
route each cable through the patch-panel tray, make sure that adequate cable slack remains.
While facing the front of the patch panel, at the rear of the patch panel, plug the eight LC-connector
Step 8
fan-out cables on the MPO cable into their corresponding connectors on the bottom row of the patch
panel. You should plug the fan-out cables from left to right (as you face the patch panel), following the
numbers tagged (1 through 8) on the cables.
Figure 3-19
the assigned wavelengths for each port on the patch panel, as indicated at the top of the patch-panel bar.
The numbers on the patch-panel bar correspond to a wavelength on the ITU grid.
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
3-76
LC-type connectors
MPO connector
shows the patch-panel connectors from the rear of the patch-panel tray.
Chapter 3
Turn Up a Node
Figure 3-20
shows
September 2005