DLP-G316 Install Fiber-Optic Cables from a TXP/MXP Node to the Patch Panel
DLP-G316 Install Fiber-Optic Cables from a TXP/MXP Node to the Patch Panel
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
At the appropriate TXP/MXP card, plug a fiber-optic cable into the TX port of the DWDM connector.
Step 1
As needed, route slack fiber-optic cable around the round cable retainers in the fiber-storage tray
Step 2
(Figure 15-38 on page
When you close the fiber-storage tray, the cables must not be pinched, and the cable bend radius must
Caution
be equal to or greater than the minimum radius that is recommended in your site specifications. As you
route each cable through the fiber-storage tray, make sure that adequate cable slack remains.
On the DWDM (front) side of the patch panel, plug the other end of the cable into the connector on the
Step 3
bottom row that corresponds to the wavelength to which the TXP/MXP port is tuned. (See
on page 3-77
Figure 3-21
Figure 3-21
Front View of the Patch Panel
.
Plug a fiber-optic cable into the RX port of the DWDM connector on that TXP/MXP card.
Step 4
On the DWDM (front) side of the patch panel, plug the other end of the cable into the connector on the
Step 5
top row that corresponds to the wavelength to which the TXP/MXP port is tuned.
Repeat Steps
Step 6
Return to your originating procedure (NTP).
Step 7
.
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
3-78
This task describes how to route fiber-optic cables from the patch panel to
TXP/MXP cards in a transponder/muxponder shelf.
TXP/MXP card(s)
Fiber-optic cable(s)
NTP-G34 Install Fiber-Optic Cables on DWDM Cards and DCUs, page
3-48
As needed
Onsite
None
15-40).
for a view of the wavelengths assigned to the patch-panel connectors).
shows the patch-panel connectors from the front of the patch-panel tray.
DEMUX connectors (to the RX ports on the TXP/MXP cards)
MUX connectors (to the TX ports on the TXP/MXP cards)
1
through
5
for all of the TXP/MXP cards that you want to connect to this patch panel.