F05064
Parallel connection: Pulse synchronization error
Message value:
-
Message class:
General drive fault (19)
Drive object:
VECTOR_G
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
POWER ON (IMMEDIATELY)
Cause:
The pulse synchronization of at least one of the power units connected in parallel is incorrect.
Remedy:
Restart the drive system.
A05065 (F, N)
Voltage measured values not plausible
Message value:
%1
Message class:
Power electronics faulted (5)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
The voltage measurement does not supply any plausible values and is not used.
Alarm value (r2124, interpret bitwise binary):
Bit 1: Phase U
Bit 2: Phase V
Bit 3: Phase W
Remedy:
The following parameterization must be made in order to deactivate the alarm:
- Deactivate voltage measurement (p0247.0 = 0).
- Deactivate flying restart with voltage measurement (p0247.5 = 0) and deactivate fast flying restart (p1780.11 = 0).
Reaction upon F:
NONE (OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F05118 (A)
Pre-charging contactor simultaneity monitoring time exceeded
Message value:
fault cause: %1, additional information: %2
Message class:
Infeed faulted (13)
Drive object:
B_INF, VECTOR_G
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A feedback signal for the pre-charging contactor (ALM, SLM, BLM diode) or the line contactor (BLM thyristor)
interconnected and the simultaneity monitoring (p0255[4, 6]) activated.
After opening or closing a contactor of the parallel connection, after a monitoring time has elapsed, not all of the
contactors have assumed the same state.
Fault value (r0949, interpret binary):
Bit 0 = 1: simultaneity error when closing the contactors.
Bit 1 = 1: simultaneity error when opening the contactors.
Bit 16 = 1: PDS0 contactor is closed.
Bit 17 = 1: PDS1 contactor is closed.
Bit 18 = 1: PDS2 contactor is closed.
Bit 19 = 1: PDS3 contactor is closed.
Bit 20 = 1: PDS4 contactor is closed.
Bit 21 = 1: PDS5 contactor is closed.
Bit 22 = 1: PDS6 contactor is closed.
Bit 23 = 1: PDS7 contactor is closed.
Note:
PDS: Power unit Data Set
Remedy:
- check the monitoring time setting (p0255[4, 6]).
- check the contactor wiring and activation.
- if required, replace the contactor.
See also: p0255 (Power unit contactor monitoring time)
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A