Fault value (r0949, interpret decimal):
yxxx dec
y = analog input (0 = analog input 0 (AI 0), 1 = analog input 1 (AI 1))
xxx = component number (p0151)
Note:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)
Remedy:
- check the wiring for interruptions.
- Check the magnitude of the injected current - it is possible that the infed signal is too low.
- Check the load resistor (250 Ohm).
Note:
The input current measured by the Terminal Module can be read out from r4052[x].
For p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)) the following applies:
A current less than 4 mA is not displayed in r4052[x] - but instead r4052[x] = 4 mA is output.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F03505 (N, A)
Analog input wire breakage
Message value:
%1
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
TM150, TM54F_MA, TM54F_SL
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The wire-break monitoring for an analog input has responded.
The input current of the analog input has exceeded the threshold value parameterized in p4061[x].
Index x = 0: Analog input 0 (X521.1/X521.2)
Index x = 1: Analog input 1 (X521.3/X521.4)
Fault value (r0949, interpret decimal):
yxxx dec
y = analog input (0 = analog input 0 (AI 0), 1 = analog input 1 (AI 1))
xxx = component number (p0151)
Note:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)
Remedy:
- check the wiring for interruptions.
- Check the magnitude of the injected current - it is possible that the infed signal is too low.
- Check the load resistor (250 Ohm).
Note:
The input current measured by the Terminal Module can be read out from r4052[x].
For p4056[x] = 3 (unipolar current input monitored (+4 ... +20 mA)) the following applies:
A current less than 4 mA is not displayed in r4052[x] - but instead r4052[x] = 4 mA is output.
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A03506 (F, N)
24 V power supply missing
Message value:
%1
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The 24 V power supply for the digital outputs (X124) is missing.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
4 Faults and alarms
4.2 List of faults and alarms
1411