Avaya S8700 Maintenance Manual page 2180

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance-Object Repair Procedures
Configuration Audit (#759)
This test is nondestructive.
NOTE:
For descriptions of result codes for this test see:
''SNC-BD (Switch Node Clock Circuit Pack)''
a Switch Node Clock (circuit pack slots 10 or 12).
''SNI-BD (SNI Circuit Pack)''
Interface (circuit pack slots 2–9 or 13–20).
This test is run via the test board short or test board long command for SNI
circuit packs or SNC circuit packs.
For SNI circuit packs, this test queries the SNI for SNCs in the same switch node
carrier, SNI peers, DS1Cs, and EI or SNI neighbors that the SNI can
communicate with and compares this data to the administered data.
For SNC circuit packs, this test queries the SNC for SNCs and SNIs in the same
switch node carrier that the SNC can communicate with and compares this data to
the administered data.
Failures of this test cause entries in the error and alarm logs against Switch Node
Configuration (SN-CONF) with the board location of the SNI or SNC.
Incorrectly Connected Administered Fibers
Some physically connected fibers that do not match fiber administration can
cause port network problems that are not detected and alarmed by PNC tests.
The symptoms will usually be many phone calls not working correctly, and port
network component alarms because of translation mismatches.
This test is unable to detect the case where an SNI is connected to the same type
of board (EI or SNI) as administered but located in a different cabinet but the
same carrier and same slot as the administered fiber endpoint. The administered
fiber endpoint can be viewed with the list fiber-link command. This test can only
detect if the fiber endpoint connected to the SNI is in a different carrier, slot
location than the administered fiber endpoint.
Incorrectly Connected Administered SNI-
to-EI Fibers
If the SNI is connected to the same type of fiber endpoint as the administered fiber
endpoint, but the location is the same as administered except for the cabinet,
many phone calls will not work correctly; some phone calls will not go through and
some phone calls will ring the wrong phone.
8-1458
Issue 1 May 2002
when the circuit pack tested is
when the circuit pack tested is a Switch Node
555-233-143

Advertisement

Table of Contents
loading

Table of Contents