Maintenance-Object Repair Procedures
Table 8-634. Test #36 Audit and Update Test — Continued
Error
Test
Code
Result
Description / Recommendation
0
NO
The test could not relate the internal ID to the port (no board). This could be
BOARD
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board's translations are correct. Use the list
2. If the board was found to be correctly inserted in step 1, issue the busyout
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the linkage
DS1 Tie Trunk Seizure Test (#136)
The DS1 Tie Trunk Seizure test is run to verify the trunk's signaling capability.
The test is composed of two parts. The first part queries the circuit pack for the
following errors: Loss of Signal, Red alarm, Blue alarm, Yellow alarm, and
Hyperactivity alarm. The second part of the test is performed by sending a
seizure message to the DS1 Interface circuit pack and expecting an active reply
by the DS1 Interface circuit pack. If maintenance software does not receive any
reply and the timer expires, the test fails. Once the active message is received, a
dial pause message is sent to the DS1 Interface circuit pack. If the DS1 Interface
circuit pack replies with a dial pulse tone message when the far end responds to
the seizure, then the DS1 tie trunk Seizure test passes. If the far end does not
respond to the seizure and the timer expires, and the DS1 Interface circuit pack
sends a reorder message back to the maintenance software, then the test fails.
This second part of this test cannot be run on a trunk if one of the following cases
is true:
1. The trunk direction is administered as an incoming only trunk.
2. The trunk is the 24
administered using 24
3. The trunk has been seized by a normal trunk call.
4. The trunk is administered with maintenance test disabled.
5. The outgoing signal type of the trunk is either automatic or immediate-start.
6. This test always passes if the associated board is the TN802 IP trunk
circuit pack.
8-1634
Issue 1 May 2002
config command, and resolve any problems that are found.
board command.
between the internal ID and the port. If this is not the case, check to see
that there is a valid board inserted.
th
port on a DS1 Interface circuit pack which is
th
common-channel signaling.
Continued on next page
555-233-143