Maintenance-Object Repair Procedures
TDM bus Clock Circuit Status Inquiry Test (#148)
The TDM bus Clock circuitry is checked for sanity. Any problems that are found
are reported via error codes
Table 8-625. Test #148 TDM bus Clock Circuit Status Inquiry Test
Error
Test
Code
Result
Description / Recommendation
None,
ABORT
The system could not allocate the necessary resources for the test.
1001
1. Wait 1-minute, and retry the test.
2000
ABORT
Response to the test was not received within the allowable time period.
2100
ABORT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1
FAIL
This error means the Tone-Clock circuit framing verification firmware reports an
error in the clock synchronization signal coming into this port network.
1. If the Tone-Clock circuit reporting the problem is a master clock, then the
2. If the Tone-Clock circuit is a slave clock, then the EI to which it is listening
3. If no problem can be found with the incoming synchronization signal,
2
FAIL
This error indicates that Tone-Clock circuit has inaccurately detected loss of
signal on the incoming synchronization timing source.
4, 8
FAIL
The local oscillator on the Tone-Clock circuit has failed.
16, 32
FAIL
The circuitry on the Tone-Clock circuit used to detect synchronization timing
errors has failed.
1. Errors 2, 4, 8, 16, and 32 indicate that there is poor synchronization
64
FAIL
This message is only sent when an uplink message has reported the loss of
valid synchronization timing information coming into this port network. It has
been reported in TDM-CLK Error Log entries; one or more of 1025, 1281, 1537,
2049 and 2305.
1. Resolve the errors indicated. No separate corrective action is required.
8-1612
Issue 1 May 2002
system synchronization reference is providing a bad timing source. See
''SYNC (Port-Network Synchronization)'' on page 8-1509
(Stratum-3 Clock)'' on page 8-1496
reference.
is providing a bad timing source. Follow the diagnostic procedures
specified for TDM-CLK Error Code 2305.
replace the IPSI or Tone-Clock circuit pack. See
Tone-Clock Circuit Pack'' on page
between port networks and external facilities. It may be noticeable to the
customer in the form of errors in data communications. The Tone-Clock
circuit is defective. See
''Replacing the IPSI or Tone-Clock Circuit Pack''
on page
8-1666.
or
to change the system synchronization
''Replacing the IPSI or
8-1666.
Continued on next page
''STRAT-3
555-233-143