p2100[0...19]
Change fault response fault number / Chng resp F_no
All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Selects the faults for which the fault response should be changed
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2101
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Messages
CU_G150_DP, TM31,
Not for motor type: -
TM120, TM150, TB30,
TM54F_MA,
Min
TM54F_SL, ENC, HUB
0
Description:
Sets the fault response for the selected fault.
Value:
0:
Dependency:
The fault is selected and the required response is set under the same index.
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
5:
6:
7:
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
NONE
NONE
OFF1
OFF2
OFF3
STOP2
Internal armature short-circuit / DC braking
ENCODER (p0491)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
0
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
7
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
535