p0199[0...24]
Drive object name / DO name
All objects
Can be changed: C1
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
0
Description:
Freely assignable name for a drive object.
In the commissioning software, this name cannot be entered using the expert list, but is specified in the configuration
assistant. The object name can be subsequently modified in the Project Navigator using standard Windows
resources.
Note:
The parameter is not influenced by setting the factory setting.
r0200[0...n]
Power unit code number actual / PU code no. act
VECTOR_G, B_INF
Can be changed: -
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
-
Description:
Displays the unique code number of the power unit.
Note:
r0200 = p0201: No power unit found
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0201[0...n]
Power unit code number / PU code no
VECTOR_G
Can be changed: C2(2)
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Dependency:
Refer to: F07815
Notice:
When p0201 = 10000, the rated power unit data is reloaded and dependent parameters are set (e.g. p0205, p0210,
p0230, p0857, p1800). p0201 is then automatically assigned the value of r0200 if the code number of the power unit
could be read. A warm start must be performed after this procedure (automatically if necessary).
Note:
The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2). However, if the comparator in p9906 or p9908 is at 2 (low) or 3 (minimum), the power unit
commissioning is automatically set to p0201 = r0200 upon exiting.
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0201[0...n]
Power unit code number / PU code no
B_INF
Can be changed: C2(2)
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
65535
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
109