Siemens G130 List Manual page 648

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r4052[0...1]
CO: TB30 analog inputs actual input voltage / TB30 AI U_inp act
TB30
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [V]
Description:
Displays the actual input voltage at the analog inputs for Terminal Board 30 (TB30).
Note:
For p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA)) the following applies:
A current less than 4 mA is not displayed in r4052[x] - but instead r4052[x] = 4 mA is output.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
AI: Analog Input
p4053[0...1]
TM31 analog inputs smoothing time constant / TM31 AI T_smooth
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
p4053[0...1]
TB30 analog inputs smoothing time constant / TB30 AI T_smooth
TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs of the Terminal Board 30
(TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
AI: Analog Input
r4055[0...1]
CO: TM31 analog inputs actual value in percent / TM31 AI value in %
TM31
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [%]
Description:
Displays the currently referred input value of the analog inputs of Terminal Module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note:
AI: Analog Input
648
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.0 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.0 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 1
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.0 [ms]
Access level: 1
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0.0 [ms]
Access level: 1
Func. diagram: 9549, 9566,
9568
Unit selection: -
Expert list: 1
Factory setting
- [%]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents