Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited. The inhibited interconnections can only be changed again after setting value 999.
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
B_INF
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
370
Description:
Sets the send and receive telegram.
Value:
370:
371:
999:
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
ENC
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
81
Description:
Sets the send and receive telegram.
Value:
81:
82:
83:
999:
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
r0924[0...1]
ZSW bit pulses enabled / ZSW pulse enab
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the position of the "Pulses enabled" status signal in the PROFIdrive telegram.
Index:
[0] = Signal number
[1] = Bit position
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
SIEMENS telegram 370, PZD-1/1
SIEMENS telegram 371, PZD-5/8
Free telegram configuration with BICO
SIEMENS telegram 81, PZD-2/6
SIEMENS telegram 82, PZD-2/7
SIEMENS telegram 83, PZD-2/8
Free telegram configuration with BICO
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 2401, 2420,
2423, 2447, 2457, 2481, 2483
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 1
Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: 2454, 2456
Unit selection: -
Expert list: 1
Factory setting
-
291