p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
B_INF
Can be changed: T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
370
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
370:
371:
999:
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
ENC
Can be changed: T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
81
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
81:
82:
83:
999:
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
p2080[0...15]
BI: Binector-connector converter status word 1 / Bin/con ZSW1
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Communications
CU_G150_DP,
Not for motor type: -
VECTOR_G, B_INF,
TM31, TM120, TM150,
Min
TB30, ENC
-
Description:
Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form status word 1.
Index:
[0] = Bit 0
[1] = Bit 1
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
SIEMENS telegram 370, PZD-1/1
SIEMENS telegram 371, PZD-5/8
Free telegram configuration with BICO
SIEMENS telegram 81, PZD-2/6
SIEMENS telegram 82, PZD-2/7
SIEMENS telegram 83, PZD-2/8
Free telegram configuration with BICO
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: 2472
Unit selection: -
Expert list: 1
Factory setting
0
527