2 Parameters
2.2 List of parameters
p4675[0...n]
Analog sensor channel B voltage per encoder period / Ana_sens B U/per
VECTOR_G, ENC
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-10.0000 [V]
Description:
Sets the output voltage range to be mapped for the connected analog sensor.
The voltage range is determined by the following parameters:
- p4674 (voltage at actual value 0)
- p4675 (voltage per encoder period)
Note:
The minimum actual value which can be mapped is equal to p4674 - p4675/2.
The maximum actual value which can be mapped is equal to p4674 + p4675/2.
p4676[0...n]
Analog sensor range limit threshold / Ana_sens lim thr
VECTOR_G, ENC
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [%]
Description:
Sets the threshold for limit monitoring of the absolute actual value on the analog sensor.
If this threshold is overshot by the actual value of a channel, a corresponding fault/alarm (p4670.9) is output.
Dependency:
Refer to: p4673, p4675
p4677[0...n]
Analog sensor LVDT configuration / Ana_sens LVDT conf
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Sets the configuration for LVDT mode on the analog sensor.
Bit field:
Bit
00
01
02
03
p4678[0...n]
Analog sensor LVDT ratio / An_sens LVDT ratio
VECTOR_G, ENC
Can be changed: C2(4)
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
0.00 [%]
Description:
Sets the ratio for the LVDT sensor.
694
Signal name
LVDT ON
Track B excitation
Fixed value amplitude
Fixed value amplitude and phase
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10.0000 [V]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
100.0 [%]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
200.00 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
6.0000 [V]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.0 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No
No
No
No
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50.00 [%]
SINAMICS G130/G150